Precautions

This section describes the considerations when the temperature control module is mounted on an extension base unit in a
redundant system with redundant extension base unit.
When configuring the temperature trace
Connect the engineering tool to the CPU module of the control system.
The engineering tool cannot recognize the temperature control module if it is connected to the CPU module of the standby
system.
Program examples
Unless otherwise specified, program examples provided in this manual and the following manual are for when the module is
used in the single CPU system or in the multiple CPU system.
MELSEC iQ-R Temperature Control Module User's Manual (Startup)
When using the module in the redundant system, refer to the following manual and observe the precautions on programming
for when using the Process CPU (redundant mode).
MELSEC iQ-R CPU Module User's Manual (Application)
Signal flow tracking setting
When using the module FBs and applying the program examples to an actual system, set "Signal Flow Memory Tracking
Setting" to "Transfer". If not, the module FBs and programs may not work properly when system switching occurs.
[CPU Parameter]  [Redundant System Settings]  [Tracking Setting]
APPX
350
Appendix 7 Using the Module in the Redundant System with Redundant Extension Base Unit