CH1 Derivative action selection
Select the type of derivative action. Selecting a derivative action suitable for each of fixed value actions and ramp actions
improves dynamic characteristics. For details on the derivative action selection function, refer to the following:
Page 55 Derivative Action Selection Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Derivative action selection
CH Derivative action selection (in the Q compatible mode)
■Setting range
• 0: Measured value derivation
• 1: Deviation derivation
■Enabling the settings
Turn ON and OFF 'Setting change command' (YB) in the setting mode ('Setting/operation mode status' (X1): OFF) to enable
the settings.
■Default value
The default value is Measured value derivation (0).
CH1 Setting variation rate limiter unit time setting
Set the unit time of the setting variation rate limiter. For details on the setting variation rate limiter setting function, refer to the
following:
Page 58 Setting Variation Rate Limiter Setting Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Setting variation rate limiter unit time setting
CH Setting variation rate limiter unit time setting (in the Q compatible mode)
■Setting range
• 0 (Unit time setting not used)
• 1 to 3600 (s)
When 0 has been set, the temperature control module operation is the same as the operation of when 60 (1 minute) has been
set.
■Enabling the settings
Turn ON and OFF 'Setting change command' (YB) in the setting mode ('Setting/operation mode status' (X1): OFF) to enable
the settings.
■Default value
The default value is 0 (unit time setting not used).
APPX
280
Appendix 3 Buffer Memory Areas
CH1
CH2
525
725
729
745
CH1
CH2
526
726
735
751
CH3
CH4
925
1125
761
777
CH3
CH4
926
1126
767
783

Advertisement

Table of Contents
loading

This manual is also suitable for:

R60tctrt2tt2R60tcrt4R60tctrt2tt2bwR60tcrt4bw

Table of Contents