Temperature Conversion Function (Using Unused
Channels)
In the heating-cooling control (normal mode), mix control (normal mode), or position proportional control (normal mode), only
the temperature measurement can be executed using unused temperature input terminals. When this function is used, the
temperature control and alert judgment are not executed.
Temperature input terminals that can be used
Temperature input terminals that can be used for this function differ depending on the control mode to be selected.
Use the MT2 (Monitor CH2), MT3 (Monitor CH3), and MT4 (Monitor CH4) terminals in the following table.
Terminal
Terminal symbol
No.
When using thermocouples (R60TCTRT2TT2,
R60TCTRT2TT2BW)
Heating-cooling
control (normal
mode)
1
L1H
2
L1C
3
L2H
4
L2C
5
COM-
6
NC/CH2A
7
CH1+/CH1B
8
CH2+/CH2B
9
CH1-/CH1b
10
CH2-/CH2b
11
NC/CH1A
12
CJ
13
NC
14
CJ
15
MT3+
16
MT4+
17
MT3-
18
MT4-
Parameters and buffer memory areas that can be used in this function
The following lists the parameters and buffer memory areas that can be used in this function.
■Parameter
• "Input range setting" of "Control basic parameters" in "Application Setting"
• "Primary Delay Digital Filter Setting" in "Application Setting"
• "Sensor Correction Value Setting" in "Application Setting"
• "Number of moving averaging" in "Application Setting"
• "Temperature conversion setting" of "Heating/cooling control setting" in "Application Setting"
• "Cold Junction Temperature Compensation Selection" in "Application Setting" (the R60TCTRT2TT2 and
R60TCTRT2TT2BW only)
• "Rate alarm alert output enable/disable setting" of "Rate alarm" in "Application Setting"
• "Rate alarm warning detection period" of "Rate alarm" in "Application Setting"
• "Rate alarm upper limit value" of "Rate alarm" in "Application Setting"
• "Rate alarm lower limit value" of "Rate alarm" in "Application Setting"
Mix control
Position
(normal mode)
proportional
control (normal
mode)
L1
CH1 OPEN
L2
CH1 CLOSE
L3H
CH2 OPEN
L3C
CH2 CLOSE
COM-
COM-
NC/MT2A
NC/CH2A
CH1+/CH1B
CH1+/CH1B
MT2+/MT2B
CH2+/CH2B
CH1-/CH1b
CH1-/CH1b
MT2-/MT2b
CH2-/CH2b
NC/CH1A
NC/CH1A
CJ
CJ
NC
NC
CJ
CJ
CH3+
MT3+
CH4+
MT4+
CH3-
MT3-
CH4-
MT4-

1.9 Temperature Conversion Function (Using Unused Channels)

When using platinum resistance thermometers
(R60TCTRT2TT2, R60TCTRT2TT2BW, R60TCRT4,
R60TCRT4BW)
Heating-cooling
Mix control
control (normal
(normal mode)
mode)
L1H
L1H
L1C
L1C
L2H
L3
L2C
L4
COM-
COM-
Not used
Not used
CH1A
CH1A
CH2A
MT2A
CH1B
CH1B
CH2B
MT2B
CH1b
CH1b
CH2b
MT2b
MT3A
CH3A
MT4A
CH4A
MT3B
CH3B
MT4B
CH4B
MT3b
CH3b
MT4b
CH4b
1
Position
proportional
control (normal
mode)
CH1 OPEN
CH1 CLOSE
CH2 OPEN
CH2 CLOSE
COM-
NC
CH1A
CH2A
CH1B
CH2B
CH1b
CH2b
MT3A
MT4A
MT3B
MT3B
MT3b
MT4b
1 FUNCTIONS