CH1 Upper limit setting limiter
Set the upper limit value of the set value (SV).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Upper limit setting limiter
CH Upper limit setting limiter (in the Q compatible mode)
■Setting range
The value is within the temperature measuring range set in 'CH1 Input range' (Un\G501). ( Page 254 CH1 Input range)
Configure the settings that satisfy the following conditions.
• 'CH1 Lower limit setting limiter' (Un\G512) < 'CH1 Upper limit setting limiter' (Un\G511)
When the above conditions are not satisfied, CH Upper/lower limit setting limiter error (error code: 1A1H) occurs.
(1)
Input lower limit
(1) 'CH1 Lower limit setting limiter' (Un\G512)
(2) 'CH1 Upper limit setting limiter' (Un\G511)
■Setting unit
The value to be set differs depending on the value stored in 'CH1 Decimal point position' (Un\G400). ( Page 229 CH1
Decimal point position)
• No decimal point (0): Set a value in increments of 1 (or digit).
• First decimal place (1): Set a value (the value multiplied by 10) in increments of 0.1 ().
■Default value
• For the R60TCTRT2TT2 and the R60TCTRT2TT2BW
The default value is 1300.
• For the R60TCRT4 and the R60TCRT4BW
The default value is 6000.
Set value (SV) setting range
CH1
CH2
511
711
55
87
(2)
Input upper limit
Appendix 3 Buffer Memory Areas
CH3
CH4
911
1111
119
151
APPX
269
A