Mitsubishi Electric MELSEC iQ-R Series User Manual page 241

Temperature control module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

CH1 Process value (PV) scaling value
When the temperature process value (PV) scaling function is enabled, a scaled temperature process value (PV) is stored. For
details on the temperature process value (PV) scaling function, refer to the following:
Page 68 Scaling Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Process value (PV) scaling value
CH Process value (PV) scaling value (in the Q compatible mode)
CH1 AT simultaneous temperature rise parameter calculation flag
The status of when the simultaneous temperature rise AT (auto tuning) calculates the simultaneous temperature rise
parameter is stored in this area.
• 0: OFF
• 1: ON
b15
0
0
0
0
0
0
Bit data from b15 to b3 are fixed to 0.
Bit
Flag name
b0
AT simultaneous temperature rise parameter
calculation completion
b1
AT simultaneous temperature rise parameter
calculation error status
b2
Simultaneous temperature rise AT disable status
b3 to b15
(Fixed to 0)
*1 The values of 'CH1 Simultaneous temperature rise gradient data' (Un\G554) and 'CH1 Simultaneous temperature rise dead time'
(Un\G555)
This area is enabled only for the following channels:
• CH1 to CH4 of when the standard control is used
• CH3 and CH4 of when the mix control (normal mode) or mix control (expanded mode) is used
For details on the simultaneous temperature rise function, refer to the following:
Page 100 Simultaneous Temperature Rise Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH AT simultaneous temperature rise parameter calculation flag
CH AT simultaneous temperature rise parameter calculation flag (in the Q
compatible mode)
to
b3
0
0
0
0
0
0
0
Description
This bit turns ON when the simultaneous temperature rise parameters
the simultaneous temperature rise AT.
This bit turns ON when the simultaneous temperature rise parameters
calculated by the simultaneous temperature rise AT.
This bit turns ON when the simultaneous temperature rise AT was not able to be executed.
(Not used)
CH1
CH2
412
612
728
744
b2
b1
b0
CH1
CH2
413
613
573
605
CH3
CH4
812
1012
760
776
*1
are calculated by
*1
cannot be
CH3
CH4
813
1013
637
669
APPX