Mitsubishi Electric MELSEC iQ-R Series User Manual page 226

Temperature control module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Control mode selection
Select a control mode. Depending on this setting, the control method of each channel changes as follows:
Setting value
0
1
2
3
4
5
6
• When the control mode has been changed, all items are overwritten with default values. Change each
parameter setting if necessary.
• A set value discrepancy error (control mode) (error code: 1910H) occurs right after the control mode
change. To clear the error, turn from OFF to ON 'Setting value backup command' (Y8) and register the
parameter after the change in the non-volatile memory.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
Control mode selection
Control mode selection (in the Q compatible mode)
■Default value
The default value is Standard control (0).
Sampling cycle selection
Select one of the following sampling cycles:
• 0: 500ms/4 channels
• 1: 250ms/4 channels
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
Sampling cycle selection
■Default value
The default value is 500ms/4 channels (0).
A set value discrepancy error (sampling cycle) (error code: 1930H) occurs right after the sampling cycle
change. To clear the error, turn from OFF to ON 'Setting value backup command' (Y8) and register the
parameter after the change in the non-volatile memory.
APPX
224
Appendix 3 Buffer Memory Areas
Control mode
Standard control
Heating-cooling control (normal mode)
Heating-cooling control (expanded mode)
Mix control (normal mode)
Mix control (expanded mode)
Position-proportional control (normal
mode)
Position-proportional control (expanded
mode)
No. of control loops
Standard control 4 loops
Heating-cooling control 2 loops
Heating-cooling control 4 loops
• Heating-cooling control 1 loops
• Standard control 2 loops
• Heating-cooling control 2 loops
• Standard control 2 loops
Position-proportional control 2 loops
Position-proportional control 4 loops
CH1
CH2
300
1025
CH1
CH2
301
No. of channels for
temperature input
2
1
2
CH3
CH4
CH3
CH4

Advertisement

Table of Contents
loading

This manual is also suitable for:

R60tctrt2tt2R60tcrt4R60tctrt2tt2bwR60tcrt4bw

Table of Contents