CH1 Control motor time
Set the control motor rotation time from the full-open state to the full-closed state.
Check the specifications of the control motor used before setting a value.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Control motor time
CH Control motor time (in the Q compatible mode)
■Setting range
The setting range is 5 to 1000 (s).
■Default value
The default value is 10 (s).
CH1 Integration output limiter setting
When one side output is continuously performed several times, each output ON time is integrated. If the integrated time
exceeds the setting value, the output is turned OFF.
When the opposite side output is turned ON while the one side output ON time is being integrated, the integrated value is
reset.
Ex.
If the control is started in the full-closed state when 'CH1 Control motor time' (Un\G528) has been set to 10 (s) and 'CH1
Integration output limiter setting' (Un\G529) has been set to 1000 (100.0%), the operation is as follows:
The open side integrated value is expressed in the ratio of the open side output ON time to the control motor time.
Open side integrated value = (Open side output ON time) / (Control motor time)  100 (%)
The open side output is turned OFF when the open side integrated value equals to the integration output limiter setting.
Open side output:
3 seconds
(open side integrated
value: 30%)
Ex.
When 'CH1 Control motor time' (Un\G528) has been set to 10 (s) and 'CH1 Integration output limiter setting' (Un\G529) has
been set to 1000 (100.0%), the operation is as follows if the opposite side output (close side output) is turned on while the
open side output ON time is being integrated.
The close side integrated value is expressed in the ratio of the close side output ON time to the control motor time.
Close side integrated value = (Close side output ON time) / (Control motor time)  100 (%)
Open side output:
3 seconds
(open side integrated
value: 30%)
APPX
282
Appendix 3 Buffer Memory Areas
Open side output:
5 seconds
Stop
(open side integrated
value: 80%)
Open side output:
5 seconds
Stop
(open side integrated
value: 80%)
CH1
CH2
528
728
1041
1057
Open side output: 4 seconds
Stop
(open side integrated
value: 100%)
Close side output: 2 seconds
Reset of the open side integrated value
Stop
(The close side integrated value newly
becomes 20%.)
CH3
CH4
928
1128
1073
1089