Transistor output monitor ON delay time setting
Set the delay time of ON delay output flag. Configure this setting to detect heater disconnections with another input module on
the system.
For ON delay output flag, refer to the following:
Page 234 CH1 Transistor output flag
For details on the ON delay output function, refer to the following:
Page 70 ON Delay Output Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
Transistor output monitor ON delay time setting
Transistor output monitor ON delay time setting (in the Q compatible mode)
■Setting range
The setting range is 0 or 1 to 50 (10 to 500ms). When 0 has been set, ON delay output flag is not set to 1 (ON).
■Default value
The default value is 0.
Manipulated value resolution change for output with another analog module
Set the resolutions of the following buffer memory areas:
• 'CH1 Manipulated value (MV)' (Un\G403)
• 'CH1 Manipulated value for heating (MVh)' (Un\G403)
• 'CH1 Manipulated value for cooling (MVc)' (Un\G408)
For details, refer to the following:
Page 71 Output
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
Manipulated value resolution change for output with another analog module
Manipulated value resolution change for output with another analog module (in
the Q compatible mode)
■Setting range
• 0: 0 to 4000
• 1: 0 to 12000
• 2: 0 to 16000
• 3: 0 to 20000
• 4: 0 to 32000
The manipulated values (MV) to which the resolutions have been reflected are stored in the following buffer memory areas:
• 'CH1 Manipulated value (MV) for output with another analog module' (Un\G407)
• 'CH1 Manipulated value for heating (MVh) for output with another analog module' (Un\G407)
• 'CH1 Manipulated value for cooling (MVc) for output with another analog module' (Un\G409)
■Enabling the settings
Turn ON and OFF 'Setting change command' (YB) in the setting mode ('Setting/operation mode status' (X1): OFF) to enable
the settings.
■Default value
The default value is 0 to 4000 (0).
CH1
CH2
307
175
CH1
CH2
308
181
Appendix 3 Buffer Memory Areas
CH3
CH4
CH3
CH4
APPX
227
A