CH1 Temperature rise completion range setting
Set the width of the temperature rise completion range. When the temperature process value (PV) satisfies the following
conditions, the temperature rise is completed.
• Set value (SV) - Temperature rise completion range Temperature process value (PV) Set value (SV) + Temperature rise
completion range
Temperature rise
completion range (+)
Set value (SV)
Temperature rise
completion range (-)
When the value set in 'CH1 Temperature process value (PV)' (Un\G402) goes within the temperature rise judgment range,
'CH1 Temperature rise judgment flag' (Un\G404) is set to Within temperature rise completion range (1). (For the time taken for
'CH1 Temperature rise judgment flag' (Un\G404) to set to Within temperature rise completion range (1) after the temperature
rise completion, set the time in 'CH1 Temperature rise completion soak time setting' (Un\G507).)
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Temperature rise completion range setting
Temperature rise completion range setting (in the Q compatible mode)
■Setting range
• In the R mode
Condition
When the temperature unit of the input range is
When the temperature unit of the input range is
When the input range is for another analog module input
• In the Q compatible mode
Condition
When the temperature unit of the input range is
When the temperature unit of the input range is
Other than above
■Default value
The default value is 1.
APPX
264
Appendix 3 Buffer Memory Areas
Setting value
CH1
506
167
Setting range
1 () to 100 ()
1 () to 100 ()
1 to 100
Setting range
1 () to 10 ()
1 () to 10 ()
1 to 10 (%) of full scale
Temperature rise
judgment range
CH2
CH3
706
906
CH4
1106