■Setting method (Alert mode and the set value (SV) to be monitored)
From the reference targets of the set value (SV), set whether to use 'CH1 Set value (SV) monitor' (Un\G406) or "Target
Value(SV) Setting" of "Control basic parameters" in "Application Setting" with the alert mode.
• When alerts need to be judged using the value in 'CH1 Set value (SV) monitor' (Un\G406), set one of the following values:
Alert mode setting
Setting value
3
4
5
6
9
10
11
12
13
14
• When alerts need to be judged using the value of "Target Value(SV) Setting" of "Control basic parameters" in "Application
Setting," set one of the following values.
Alert mode setting
Setting value
15
16
17
18
19
20
21
22
23
24
1 FUNCTIONS
76
1.25 Alert Function
Alert mode name
Upper limit deviation alert
Lower limit deviation alert
Upper/lower limit deviation alert
Within-range alert
Upper limit deviation alert with wait
Lower limit deviation alert with wait
Upper/lower limit deviation alert with wait
Upper limit deviation alert with re-wait
Lower limit deviation alert with re-wait
Upper/lower limit deviation alert with re-wait
Alert mode name
Upper limit deviation alert (use set value (SV) setting value)
Lower limit deviation alert (use set value (SV) setting value)
Upper/lower limit deviation alert (use set value (SV) setting value)
Within-range alert (use set value (SV) setting value)
Upper limit deviation alert with wait (use set value (SV) setting value)
Lower limit deviation alert with wait (use set value (SV) setting value)
Upper/lower limit deviation alert with wait (use set value (SV) setting value)
Upper limit deviation alert with re-wait (use set value (SV) setting value)
Lower limit deviation alert with re-wait (use set value (SV) setting value)
Upper/lower limit deviation alert with re-wait (use set value (SV) setting value)