Mitsubishi Electric MELSEC iQ-R Series User Manual page 281

Temperature control module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

CH1 Cooling method setting [Q compatible mode]
Set a cooling control method in the heating-cooling control. Select a cooling method suitable for cooling characteristics of
devices.
The following figure shows the channel assignment of this buffer memory area.
to
to
b15
b12 b11
CH4
CH3
For details on the cooling method setting function, refer to the following:
Page 34 Cooling Method Setting Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Cooling method setting (in the Q compatible mode)
■Setting range
• 0H: Air cooling
• 1H: Water cooling
• 2H: Linear
■Enabling the settings
TurnON and OFF 'Setting change command' (YB) in the setting mode ('Setting/operation mode status' (X1): OFF) to enable
the settings.
■Default value
The default value is Air cooling (0H).
CH1 Overlap/dead band setting
Configure the overlap/dead band setting. For details on the overlap/dead band function, refer to the following:
Page 29 Overlap/dead Band Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Overlap/dead band setting
CH Overlap/dead band setting (in the Q compatible mode)
■Setting range
• In the R mode
Setting value
(-(Full scale of the input range)) to -1
0
1 to the full scale of the input range
• In the Q compatible mode
Setting value
-100 to -1 (-10.0 to -0.1%)
0
1 to 100 (0.1 to 10.0%)
■Default value
The default value is None (0).
to
b3
to
b8
b7
b4
CH2
CH1
b0
CH1
CH2
719
CH1
CH2
524
724
723
739
Appendix 3 Buffer Memory Areas
CH3
CH4
CH3
CH4
924
1124
755
771
Description
Overlap
None
Dead band
Description
Overlap
None
Dead band
APPX
279
A