Temperature control module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

2.
Select the module to which the sensor
correction is executed and click the
[OK] button.
3.
Select "Sensor Correction" from the
following:
[Option]  [Sensor correction]
4.
Select a channel to which the sensor
correction is executed for "Target
Channel."
5.
Select "Sensor Two-point Correction"
for "Sensor Correction Function
Selection."
6.
Monitor "Process value" and input the
* 1
correction offset value.
7.
Set the temperature process value
(PV) corresponding to the input for
"Offset Value." After setting the value,
click the [Offset Setting] button.
8.
Click the [Yes] button.
9.
Click the [OK] button.
10.
Monitor "Process value" and input the
correction gain value. After setting the
value, click the [Gain Setting] button.