Mitsubishi Electric MELSEC iQ-R Series User Manual page 112

Temperature control module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■When 'CH1 Auto tuning command' (Y4) is turned from OFF to ON in the setting mode and the
mode is shifted to the operation mode
After the mode is shifted to the operation mode ('Setting/operation mode command' (Y1) is turned from OFF to ON), the
simultaneous temperature rise parameter and PID constants are changed by the auto tuning.
Temperature
process value
(PV)
'Setting/operation mode status'
(X1)
'CH1 Auto tuning status'
(X4)
'CH1 Auto tuning command'
(Y4)
CH1 PID auto-correction status
(Un\G411, b0)
CH1 Simultaneous temperature
rise parameter correction status
(Un\G411, b1)
CH1 Simultaneous temperature
rise parameter error status
(Un\G411, b9)
CH1 Self-tuning error
(Un\G411, b10)
CH1 AT simultaneous
temperature rise parameter
calculation completion
(Un\G413, b0)
CH1 AT simultaneous
temperature rise parameter
calculation error status
(Un\G413, b1)
1 FUNCTIONS
110
1.32 Simultaneous Temperature Rise Function
Dead time
Simultaneous
temperature rise AT start
ON
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Maximum gradient
ON
Auto tuning waveform
Time
'CH1 Self-tuning flag'
(Un\G411)
'CH1 AT simultaneous
temperature rise
parameter calculation
flag' (Un\G413)