Setting method
The following shows the setting method.
1.
Set "Simultaneous temperature rise function enable/disable between multiple module" to "Enable."
[Navigation window]  [Parameter]  Target module  [Base Setting]  [Multiple module interaction function] 
[Simultaneous temperature rise function enable/disable between multiple module]
2.
Set only one module of all the temperature control modules that use the inter-module simultaneous temperature rise
function to "Master" in "Simultaneous temperature rise function master/slave selection between multiple module."
3.
Set the values calculated by the auto tuning or self-tuning or the ones that users calculated for Simultaneous
temperature rise dead time and Simultaneous temperature rise gradient data.
4.
Set groups in "Simultaneous temperature rise group setting." The inter-module simultaneous temperature rise function is
not executed to the channel that has been set to "Do not rise temperature simultaneously."
[Navigation window]  [Parameter]  Target module  [Application Setting]  [Simultaneous temperature rise setting]
 [Simultaneous temperature rise group setting]
5.
Simultaneously turn from OFF to ON 'Setting/operation mode command' (Y1) of the temperature control modules that
execute the inter-module simultaneous temperature rise.
1 FUNCTIONS
1.33 Inter-module Link Function