CH1 Overshoot suppression level setting
Overshoots at the startup and the set value (SV) change are suppressed.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Overshoot suppression level setting
CH Overshoot suppression level setting (in the Q compatible mode)
■Setting range
The setting range is 0 to 4.
When 0 is set, overshoots are not suppressed.
■Default value
The default value is 0.
CH1 Primary delay digital filter setting
The temperature process value (PV) are smoothed and sudden changes are absorbed by using the primary delay digital filter.
When the primary delay
digital filter is not set
When the primary delay
digital filter is set
The time for the temperature process value (PV) to change by 63.3% can be set by the primary delay digital filter setting (filter
setting time).
When the primary delay
digital filter is not set
When the primary delay
digital filter is set
(1) 'CH1 Primary delay digital filter setting' (Un\G563)
APPX
310
Appendix 3 Buffer Memory Areas
Temperature
process value (PV)
Temperature
process value (PV)
Temperature
process value (PV)
Temperature
process value (PV)
63.3%
CH1
CH2
562
762
1050
1066
(1)
CH3
962
1082
Time
Time
Time
Time
CH4
1162
1098