Mitsubishi Electric MELSEC iQ-R Series User Manual page 104

Temperature control module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Ex.
When channels are divided as follows
• CH1, CH2: Group 1
• CH3, CH4: Group 2
'Setting/operation mode command' (Y1)
'
CH1 Simultaneous temperature rise status
*1
(Un\G414)
'
and
CH2 Simultaneous temperature rise status
*1
(Un\G614)
'
CH3 Simultaneous temperature rise status
*1
(Un\G814)
'
and
CH4 Simultaneous temperature rise status
*1
(Un\G1014)
*1 Although Simultaneous temperature rise in process (1) is set at the start of the simultaneous temperature rise, Simultaneous
temperature rise not in process (0) is set before the completion of the temperature rise.
• When the mode is changed from the operation mode to the setting mode ('Setting/operation mode
command' (Y1) is turned from ON to OFF) during the simultaneous temperature rise, the control stops. In
addition, 'CH1 Simultaneous temperature rise status' (Un\G414) changes from Simultaneous temperature
rise in process (1) to Simultaneous temperature rise not in process (0). (An error does not occur.)
• When the simultaneous temperature rise function is executed, the setting variation rate limiter cannot be
used.
Conditions to execute the simultaneous temperature rise function
When all of the following conditions are satisfied, the simultaneous temperature rise function can be executed.
• The control is started
• The set value (SV) is larger than the temperature process value (PV).
• "Standard Control" has been selected for "Control mode selection" in "Base Setting" (This function cannot be executed in
the heating-cooling control).
• The simultaneous temperature rise parameter has been determined (or has been set) and a value other than 0 (default
value) has been set.
When a value smaller than 100% is set for the following parameter, temperature rise may not be completed at the same time.
• "Upper limit output limiter" of "Limiter setting" in "Application Setting"
1 FUNCTIONS
102
1.32 Simultaneous Temperature Rise Function
Temperature process value (PV)
CH1 Set value (SV)
CH2 Set value (SV)
CH3 Set value (SV)
CH4 Set value (SV)
OFF
'
0
'
'
0
'
Temperature rise start
ON
1
1
Executed by the temperature control module
Matches temperature rise
completion time in each group
Group 1
Group 2
arrival point
arrival point
0
0
Time