Mitsubishi Electric MELSEC iQ-R Series User Manual page 135

Temperature control module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Setting example
Ex.
When an interrupt program (I50) is executed in CH1 at the occurrence of a loop disconnection
• Parameter setting
Set "Interrupt setting" of the parameter as follows:
No.
4
• Label setting
Classification
Label name
Module label
RCPU.stSM.bAlways_ON
RCPU.stSM.bAfter_RUN1_Scan_ON
R60TC_1.stInterruptSettingData2_D.unInterrupt
FactorMask_D[3].0
R60TC_1.stInterruptSettingData2_D.unInterrupt
FactorResetRequest_D[3].0
Label to be defined
Define global labels as follows:
RCPU.stSM.bAfter_RUN1_Sc
an_ON
SM402
(0)
(8)
I50
RCPU.stSM.bAlways_ON
(10)
SM400
(18)
(19)
Condition target setting
Alert definition (Loop disconnection)
Condition target channel
setting
CH1
Description
Always ON
One scan ON after RUN
Interrupt factor mask
Interrupt factor reset request
I50
SIMASK
R60TC_1.stInterruptSettingData2_D.unInterruptFact
SET
R60TC_1.stInterruptSettingData2_D.unInterruptFact
SET
SET
Interrupt pointer
I50
Device
SM400
SM402
U0\G127.0
U0\G159.0
K1
EI
orMask_D[3].0
U0\G127.0
FEND
orResetRequest_D[3].0
U0\G159.0
G_bDisconnectDetection
F0
IRET
END
1 FUNCTIONS
1.40 Interrupt Function
1
133