2.5

Refresh Settings

Setting method
Set the buffer memory areas of the temperature control module to be automatically refreshed.
Configuring the refresh settings eliminates the need of a program for reading/writing data.
1.
Start parameters.
[Navigation window]  [Parameter]  [Module Information]  Target module  [Refresh]
2.
Click "Target" and set a refresh destination.
• When "Target" is "Module Label"
Set whether to enable or disable the auto refresh by setting "Latest error code" to "Enable" or "Disable."
• When "Target" is "Refresh Data Register (RD)"
The transfer destinations of all items are automatically set by setting a start device name for "Top Device Name."
• When "Target" is "Device"
Double-click the item to be set, and enter a value.
3.
Click "Refresh Group" and set the timing to execute the auto refresh.
Set "Refresh Group" to "At the Execution Time of END Instruction" or "At the Execution Time of Specified Program."
When setting "At the Execution Time of Specified Program," double-click "Group [n](n: 1 to 64)" and set a value of 1 to 64.
2 PARAMETER SETTING
139
2.5 Refresh Settings
2