DC Power Cable Specifications for the MX240 Router

DC Power Cable Lug Specifications—The accessory box shipped with the router includes the cable lugs
that attach to the terminal studs of each power supply (see
Figure 20: DC Power Cable Lug
End view
0.28
diameter
0.55
each hole
0.08
0.25
0.625
CAUTION:
lug to the grounding and power cables that you supply. A cable with an incorrectly
attached lug can damage the router.
NOTE:
The same cable lug is used for the grounding cable.
DC Power Cable Specifications—You must supply four DC power cables that meet the following
specifications: 6-AWG (13.3 mm
SEE ALSO
Connecting Power to a DC-Powered MX240 Router with Normal-Capacity Power Supplies | 248
Installing an MX240 DC Normal Capacity Power Supply | 390
Connecting an MX240 DC Power Supply Cable | 254
Calculating Power Requirements for MX240 Routers | 196
DC Power Source Cabling for the MX240 Router | 63
Site Electrical Wiring Guidelines for MX Series Routers | 509
2.25
Crimp area
All measurements in inches
0.37
Before router installation begins, a licensed electrician must attach a cable
2
), minimum 60° C wire, or as required by the local code.
Figure 20 on page
65).
6 AWG conductor