Omron SYSMAC CS Series Operation Manual page 58

Customizable counter units
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Names and Functions of Parts
Programming Device
Connection Switch
Note
Peripheral Port
I/O Connector
(All Units)
Special I/O Connector
(CS1W-HCP22-V1/HCA22-
V1/HCA12-V1 Only)
Indicators
Indicator
Name
RUN
Running
OPN
Program execu-
tion
38
Turn ON this switch to enable Programming Device servicing at the peripheral
port and turn it OFF to disable it. Operational errors related to the connection
of a Programming Device (such as changes in the operating mode) can be
prevented by turning OFF this switch.
Programming Device connection
switch
Set to ON:
TOOL
Set to OFF:
TOOL
1. If the switch is turned OFF, Programming Device servicing is not performed
and so the scan time is shorter.
2. This switch can also be used as a restart switch for connection with the
Programming Device.
The peripheral port is used for connecting to a Programming Device (i.e., a
Support Software installed on a computer or a Programming Console).
Note The Unit automatically recognizes the serial communications mode (i.e., Pro-
gramming Console bus, peripheral bus).
The I/O connector is for contact I/O. Make a cable for this connector with the
24-pin connector provided with the Unit. (For details, refer to 3-3 Wiring.)
The special I/O connector is for special I/O: Pulse inputs and pulse outputs for
the CS1W-HCP22-V1, pulse inputs and analog outputs for the CS1W-HCA22-
V1, and pulse inputs, analog input and analog outputs for the CS1W-HCA12-
V1. Either make a cable for this connector with the 40-pin connector provided
with the Unit, or using a special OMRON cable, connect to an OMRON Con-
nector Terminal Conversion Unit. (For details, refer to 3-3 Wiring.)
Color
Status
Green
Lit
Not lit
Green
Lit
Not lit
Connection enabled
(The switch must be turned ON to use a
ON
OFF
Programming Device.)
Connection disabled
ON
OFF
(Turn OFF the switch to prevent
operational errors.)
HCP22-V1
Meaning
The Unit is operating normally.
One of the following:
• The system in the Unit is stopped.
• The Unit is performing initialization processing.
• There is a hardware error at the Unit.
• There is no power supply from the Power Supply Unit.
• Unit WDT error.
• Unit recognition error (recognized as CPU Bus Unit)
• Unit not recognized (The data for this Unit in the registered
I/O table does not correspond with the mounted Unit.)
• CPU bus error
• Unit number error
• Unit RAM error
The Unit's program is being executed.
The Unit's program is stopped.