Omron SYSMAC CS Series Operation Manual page 52

Customizable counter units
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Performance Specifications
32
Item
Accuracy
• Voltage input
±0.2% (23±2°C)
±0.4% (0 to 55°C)
• Current input
±0.4% (23±2°C)
±0.6% (0 to 55°C)
A/D conversion time
0.05 ms max.
Input response time
1.5 ms or less (See Specification of Analog Input Functions
on page 155 for details.)
Output hold mode
Analog output values can be held. (Analog values can be
output at their peak, held, or cleared values when the Con-
version Enable Flag is OFF, a fatal error occurs, or an ana-
log output error occurs.)
Analog input refresh
Refreshing of analog outputs is set to one of the following:
method
END refresh
Immediate refresh via instructions
Offset/gain adjust-
The offset or gain can be specified and changed.
ment
Applicable Instruc-
Analog input value can be read directly with PRV.
tions
Analog Outputs
Item
Number of outputs
2 outputs
Output signal ranges Each output can be set to any one of the following: 1 to 5 V,
0 to 5 V, 0 to 10 V, or –10 to 10 V
±0.3%
Accuracy
Resolution
–10 to 10 V: 1/10,000
0 to 10 V, 0 to 5 V, or 1 to 5 V: 1/4,000
D/A conversion time
0.05 ms max.
Output function
Each analog output can be set whether output is valid or
validity
invalid.
Output hold mode
Analog output values can be held. (Analog values can be
output at their peak, held, or cleared values when the Con-
version Enable Flag is OFF, a fatal error occurs, or an ana-
log output error occurs.)
Analog output
Refreshing of analog outputs is set to one of the following:
refresh method
END refresh
Immediate refresh via instructions
Offset/gain adjust-
The offset or gain can be specified and changed.
ment
Applicable Instruc-
Analog output can be controlled directly with SPED and
tions
ACC.