Omron SYSMAC CS Series Operation Manual page 45

Customizable counter units
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Performance Specifications
Item
Other memory
Read-only por-
areas
tion of DM
Area
Trace memory
2-1-4
Functions
Types of inter-
Input interrupts
rupts
(4 points max.)
Interval timer
interrupt (1
point)
CS1W-HCP22-
V1 (pulse I/O)
CS1W-HCA22-
V1/HCA12-V1
(pulse inputs
and analog out-
puts)
Error Log Area 56 words: DM 6144 to DM 6199
Data in this area is held (with super-capacitor backup) at power inter-
ruptions or when the mode is switched.
General-pur-
400 words: DM 6200 to DM 6599
pose read-only
Data in this area is held (in flash memory) at power interruptions or
area
when the mode is switched.
Writing to this area is not possible using instructions; it is only possible
from the Programming Device. (Reading is possible with either
method.) Data in this area is protected from being changed by the lad-
der program.
Unit Setup
56 words: DM 6600 to DM 6655
Area
This area is for making the initial settings for the functions of the Cus-
tomizable Counter Unit at a software level.
Data in this area is held (in flash memory) at power interruptions or
when the mode is switched.
Writing to this area is not possible using instructions; it is only possible
from the Programming Device. (Reading is possible with either
method.) Data in this area is protected from being changed by the lad-
der program.
None
Item
Input Interrupt Mode
Counter Mode
Scheduled Interrupt Mode
One-shot Interrupt Mode
Pulse inputs
Target value
(high-speed
interrupts
counter)
Pulse out-
Target value
puts
interrupts
Pulse inputs
Target value
(high-speed
interrupts
counter)
Specifications
Specifications
Interrupt is executed in response to
input to the Unit's built-in input points
(input bits 00000 to 00003). Interrupts
can be executed when the corre-
sponding input turns ON, OFF, or
both. The response time between the
input conditions being satisfied and
execution of the interrupt program is
0.08 ms (for execution at ON).
Interrupt is executed after input is
received via the Unit's built-in input
points a certain number of times. The
number of times is counted decremen-
tally when the corresponding input
turns ON, OFF, or both.
Program is interrupted at regular intervals measured by
one of the Unit's internal timers.
Program is interrupted once after a certain time measured
by one of the Unit's internal timers.
Interrupt is executed when the high-speed counter PV is
equal to a target value set with the CTBL instruction.
Interrupt is executed when the pulse output PV is equal to
a target value set with the CTBL instruction.
Interrupt is executed when the high-speed counter PV is
equal to a target value set with the CTBL instruction.
Section 2-1
Note 1:
Specify the mode
as either Input
Interrupt Mode or
Counter Mode
using the INT
instruction.
Note 2:
Specify ON, OFF,
or both in the Unit
Setup Area.
25

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cs1w-hca12-v1Cs1w-hca22-v1Cs1w-hcp22-v1Cs1w-hio01-v1