AR Area
Address
Bits
AR 18
00
Analog Output 1
Adjustment Enable
01
Analog Output 2
Adjustment Enable
02
Adjusted Mode
Adjustment Item
03
(Reserved by system.)
04
Adjustment Up Bit
05
Adjustment Down Bit While this bit is ON, the offset value or the
06
Adjustment Clear
(reset to factory set-
tings)
07
Adjustment Set
08
Adjustment Com-
mand Operation Error
09 to 14
(Reserved by system.)
15
Adjustment Mode
Operation
AR 19
00 to 15
Analog Output 1/
Analog Output 2 Set-
ting Offset Monitor
AR 20
00 to 15
Analog Output 1/
Analog Output 2 Set-
ting Gain Monitor
Function
ON: Adjustment enabled
OFF: Adjustment disabled
Enabled in adjustment mode (DM 6631 in
Unit Setting Area set to 5A5A Hex).
Specifies either the offset value or the gain
value as the item to be adjusted.
OFF: Offset value
ON: Gain value
The value specified here can be adjusted
with the Adjustment Up Bit or Adjustment
Down Bit.
While this bit is ON, the offset value or the
gain value increases by 1 (resolution) every
0.5 s.
gain value decreases by 1 (resolution) every
0.5 s.
ON: Cleared.
OFF: Not cleared.
Enabled in adjustment mode (DM 6631 in
Unit Setting Area set to 5A5A Hex).
The adjustment value is written when this bit
is turned ON after adjusting the value with
the Adjustment Up Bit and Adjustment Down
Bit.
This flag turns ON when an operational error,
such as turning ON both the Adjustment Up
Bit and the Adjustment Down Bit together,
has been made.
ON during adjustment mode (DM 6631 in
Unit Setting Area set to 5A5A Hex).
Enabled in adjustment mode (DM 6631 in
Unit Setting Area set to 5A5A Hex).
It is possible to write gain values and offset
values here directly without using the Adjust-
ment Up Bit or Adjustment Down Bit.
Offset values:
–10 to 10 V:
0 to 10 V, 0 to 5 V, 1 to 5 V:
Gain values:
–10 to 10 V:
0 to 10 V, 0 to 5 V, 1 to 5 V:
Details
FE0C to 01F4 Hex
FF38 to 00C8 Hex
1194 to 157C Hex
0ED8 to 1068 Hex
Section 6-4
Controlled
Forced
by
set/reset
User
Enabled
Unit
Unit/User
109