Omron SYSMAC CS Series Operation Manual page 134

Customizable counter units
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

AR Area
Address
Bits
AR 09
05
ABS encoder input
commands
06
07
08 to 15 (Reserved by system.)
AR 10
00 to 15 High-speed counter 1
monitor data
AR 11
00 to 15
AR 12
00 to 15 (Reserved by system.)
AR 13
00 to 15
AR 14
00 to 15 Analog Output 1 Out-
put Value
AR 15
00 to 15 Analog Output 2 Out-
put Value
114
Function
ABS offset
preset
ABS PV pre-
set
ABS No. of
rotations
read
Range com-
parison
result
Output bit
pattern
If END refresh is set as the analog output method,
the value set here by the user in 4-digit hexadeci-
mal is output from analog output 1 when analog
output is refreshed.
If immediate refresh using instructions is set as the
analog output method, the value output from ana-
log output port 1 is stored here in 4-digit hexadeci-
mal for monitoring when analog output is
refreshed.
0 to 10 V, 0 to 5 V, 1 to 5 V:
–10 to 10 V:
Note 1: The analog output method (END refresh or
immediate refresh using instructions) is specified in
bits 00 to 07 of DM 6630 in the Unit Setup Area (00
Hex: END refreshing). The setting applies to both
analog outputs 1 and 2.
Note 2: The output signal range is specified in
DM 6613.
Same as above (except that analog output 2 is
used for analog output and the output signal range
is set in DM 6614).
Details
0: No preset
0 to 1: Offset value obtained from
multi-turn data from servo driver and
the No. of initial incremental pulses
are stored in ABS offset value (DM
6645/6646). When defining machine
origin, difference between machine
and encoder's origins is preset to
DM 6645/6646 as ABS offset value.
0: ABS PV preset invalid
0 to 1: At this point, "ABS PV" is
stored in high-speed counter PV 1
(AR 00 to 01).
0: No. of rotations data read from
servo driver invalid
1: At the rise, SEN is output to servo,
and multi-turn data is received at
phase A input.
The instruction execution result that
is output when the CTBL instruction
is executed for a range comparison
is stored here.
Bits 00 to 15: ON for each condition
(from 1 to 16) that is satisfied.
OFF: Condition not satisfied
ON: Condition satisfied
The output bit pattern that is output
when the CTBL instruction is exe-
cuted for a range comparison is
stored here.
Note: When more than one condi-
tion is satisfied, the logical OR of all
the output patterns that satisfy the
conditions is set.
FF38 to 1068 Hex
EA84 to 157C Hex
Section 6-4
Controlled
Forced
by
set/reset
User
Enabled
Unit
Immediate
refresh
using
instruc-
tions: Unit
END
refresh:
User