AR Area
Address
Bits
AR 08
06
High-speed counter 1
status
07
08
High-speed counter 2
status
09
10
11
12 to 13
14
15
Function
Measur-
ing Flag
(measure-
ment
modes 1
or 2)
High-
speed
Counter
Operating
Flag
Target
Value
Compari-
son Flag
Overflow/
Underflow
Flag
(Reserved
by sys-
tem.)
Phase-Z
Input
Reset
Flag (ON
for one
cycle)
(Reserved
by sys-
tem.)
Measur-
ing Flag
(measure-
ment
modes 1)
High-
speed
Counter
Operating
Flag
Details
OFF: Measurement for high-speed
counter rate of change or fre-
quency measurement is not in
progress.
ON: Measurement for high-speed
counter rate of change or fre-
quency measurement is in
progress. After the Measurement
Start Bit (bit 02 in AR 09) is turned
ON, this flag turns ON when sam-
pling starts (in measurement mode
1) or after 2 ms has elapsed (in
measurement mode 2).
Note: This flag is valid only when
the measurement mode set in the
Unit Setup Area (DM 6606 and
DM 6608) is set to high-speed
counter rate of change (measure-
ment mode 1) or frequency mea-
surement (measurement mode 2).
OFF: High-speed counter is
stopped.
ON: High-speed counter is operat-
ing.
Same as for high-speed counter 1
status.
Section 6-4
Controlled
Forced
by
set/reset
Unit
Enabled
101