Omron SYSMAC CS Series Operation Manual page 50

Customizable counter units
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Performance Specifications
30
■ CS1W-HCA22-V1 (Pulse Inputs and Analog Outputs)
Pulse Inputs (High-speed Counters)
same as CS1W-HCP22-V1
Analog Outputs
Item
Number of outputs
Output signal ranges Each output can be set to any one of the following: 1 to 5 V,
Accuracy
Resolution
D/A conversion time
Output function
validity
Output hold mode
Analog output
refresh method
Offset/gain adjust-
ment
Applicable Instruc-
tions
Contents
2 outputs
0 to 5 V, 0 to 10 V, or –10 to 10 V
±0.3%
–10 to 10 V: 1/10,000
0 to 10 V, 0 to 5 V, or 1 to 5 V: 1/4,000
0.05 ms max.
Each analog output can be set whether output is valid or
invalid.
Analog output values can be held. (Analog values can be
output at their peak, held, or cleared values when the Con-
version Enable Flag is OFF, a fatal error occurs, or an ana-
log output error occurs.)
Refreshing of analog outputs is set to one of the following:
END refresh
Immediate refresh via instructions
The offset or gain can be specified and changed.
Analog output can be controlled directly with SPED and
ACC.
Section 2-1