Omron SYSMAC CS Series Operation Manual page 137

Customizable counter units
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

AR Area
Address
Bits
AR 19
00 to 15 Adjustment mode
command (valid when
DM6631 = 5A5A Hex)
AR 20
00 to 15
AR 19
00 to 15
AR 20
00 to 15
AR 21
00 to 15 (Reserved by system.)
AR 22
00 to 15
AR 23
00 to 15 Adjustment mode
command (valid when
DM 6631 = 5A5A Hex)
Function
Analog Input Offset
Common for
both Analog
output 1/2
Analog Input Aver-
Details
Under the condition of
value
adjustment enable flag (AR
08 bit 00/03) being ON,
analog input offset value
can be monitored here.
-10 to +10 V: F556 to AAA
Hex
0 to 10 V: FAAB to 555 Hex
0 to 5 V: FD56 to 2AA Hex
1 to 5 V: 888 to CCC Hex
Gain
Under the condition of
value
adjustment enable flag (AR
08 bit 00/03, AR 08 bit 02)
being ON, analog input
gain value can be moni-
tored here.
-10 to +10 V: 7554 to 5FFF
Hex
0 to 10 V: 6FFF to 6554
Hex
0 to 5 V: 37FF to 32AA Hex
1 to 5 V: 3777 to 3333 Hex
Set-
Enabled in adjustment
ting
mode (DM 6631 in Unit
Offset
Setting Area set to 5A5A
Moni-
Hex).
tor
It is possible to write gain
values and offset values
Set-
here directly without using
ting
the Adjustment Up Bit or
Gain
Moni-
Adjustment Down Bit.
tor
• Offset values:
–10 to 10 V:
FE0C to 01F4 Hex
0 to 10 V, 0 to 5 V, 1 to 5 V:
FF38 to 00C8 Hex
• Gain values:
–10 to 10 V:1194 to 157C
Hex
0 to 10 V, 0 to 5 V, 1 to 5 V:
0ED8 to 1068 Hex
This indicates the number
age
of times of an average
No. of
value specified for offset/
times
gain value monitor in
in
adjustment mode.
adjust-
Average No. of times: 0000
ment
to 0040 Hex (0 to 64 times)
mode
Set this value before turn-
ing ON adjustment enable
flag.
Section 6-4
Controlled
Forced
by
set/reset
Unit
Disabled
Unit/User
User
117

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cs1w-hca12-v1Cs1w-hca22-v1Cs1w-hcp22-v1Cs1w-hio01-v1

Table of Contents