6.3

Loading firmware

New firmware versions
If a new firmware version is available for the module, you will find this on the Internet pages
of Siemens Industry Online Support under the following ID:
Link: (https://support.industry.siemens.com/cs/ww/en/ps/15920/dl)
Save the firmware file on the PC with the configuration data of the RTU.
Downloading new firmware files
You load a new firmware file from the configuration PC on the RTU via the WBM.
You will find a description of establishing the connection to the RTU from the configuration
PC in the section Establishing a connection to the WBM of the RTU (Page 81).
You will find a description of loading a firmware file via the WBM of the RTU in the section
Firmware (Page 101).
6.4

Resetting to factory settings

Resetting to factory settings: Effect
Note
Data on the RTU will be deleted
With the functions for resetting to factory settings described here, all configuration data and
process data on the RTU is deleted!
Note
RTU no longer reachable via VPN or HTTPS
When you reset to factory settings, the VPN configuration is deleted and the RTU is no
longer reachable via VPN or HTTPS.
● Deleted data
The following data is deleted by resetting to factory settings:
– IP address of the LAN interface configured by the user
– All other configuration data in the memory of the RTU
– All process data in the memory of the RTU
– Configuration data on a plugged in SD card. The file "default.cfg" on the SD card is
RTU3030C
Operating Instructions, 09/2017, C79000-G8976-C382-04
It is reset to the default factory set IP address 192.168.0.3.
deleted.
Diagnostics and maintenance
6.3 Loading firmware
257