5.6.8

Week timer

Requirement
Requirement for a precise calculation is the time-of-day synchronization of the RTU.
Function
For the week time, three times (cams) can be specified per week using the function
parameters during which the output is set to 1.
If you select the "Pulse" option, at the turn on time only a single pulse with the length of an
update cycle is set at the output instead of being permanently ON. When the "Pulse" option
is selected, the behavior applies to all three cams.
The switching status of the week timer depends on the status of all three cams.
The three cams can overlap in time. If on and off times overlap, this will cause a conflict. In
this case, the earliest on and off times have priority. Example:
Table 5- 1
Cam
1
2
3
In this example the working time is 1:00 h to 1:40 h.
Parameters
Parameters
Input parameters
En
Function parameters
M T W T F S S
ON1 .. ON3
OFF1 .. OFF3
Pulse
Output parameters
Output
RTU3030C
Operating Instructions, 09/2017, C79000-G8976-C382-04
Example of overlapping cams
On time
1:00 h
1:10 h
1:20 h
Range of values
ON / OFF
[hh:mm]
ON / OFF
Digital output / bit
memory
Off time
2:00 h
1:50 h
1:40 h
Description
Enable parameter, see section Often used parameters
(Page 198).
Check box for specifying the weekdays (three periods of
time)
Select the active weekdays by clicking on the day check
box.
Input boxes for three turn on times
Input boxes for three turn off times
The enabled option only sets pulses at the output instead
of permanently ON.
Tag in which the value calculated by the block is output.
Programming
5.6 Blocks for time functions
217