Elapsed Time Counter - Siemens SIMATIC RTU3030C Operating Instructions Manual

Telecontrol - rtu
Hide thumbs Also See for SIMATIC RTU3030C:
Table of Contents

Advertisement

Parameters
Turn on threshold
Direction
Output parameters
Counted value
Counter status
5.8.2

Elapsed time counter

Function
The block counts the operating time after the positive edge change at the "Trigger" input
parameter.
Only via the input parameter "Reset", is the counter reset to 0 or the Initial value.
If the output should not start at the value 0, you can specify a different start value using the
function parameter "Initial value".
The current total counted value is output at the output as an unsigned 32-bit value in every
update cycle.
RTU3030C
Operating Instructions, 09/2017, C79000-G8976-C382-04
Tag type / range of
Description
values
0 .. 4294967295
Threshold value for the counted value. Switches the
"Counter status" output depending on the count direction.
Decremental
Incremental
Analog memory bit
Tag in which the totaled counted value is output. If there
is overflow (4294967295) the counter starts again at
0 .. 4294967295
zero.
Digital output / bit
Tag that is set to 1 if the value of "Turn on threshold" is
memory
overshot or undershot.
The output is reset to 0 if the following events occur:
5.8 Counter and summation blocks
Incremental counting: If "Turn on threshold" is
reached (exceeded), the "Counter status" output is
set to 1.
Decremental counting: If "Turn on threshold" is
reached (undershot), the "Counter status" output is
set to 1.
Count down
Count up
Incremental counting: Reset if "Turn on threshold" is
undershot or if the "Reset" input = 1 or if the counter
overflows (value = 0)
Decremental counting: Reset if "Turn on threshold" is
overshot
Programming
231