4.20.4

DNP3

Parameters
Here you configure the data of the communications partner (master) and the transfer settings
for connection establishment.
● Active
Enable the option to enable the communication between the RTU and its communications
partner.
● IP address partner
IP address of the master
● IP address of the redundant partner
– If you use a redundant master, here configure the IP address of the second device of
– If you do not use a redundant master, here configure the IP address of the master.
● Port number
Number of the listener port of the RTU
Range of values: 1024 .. 65535
Default: 20000:
● Station address
Outstation number of the RTU
Range of values: 0 .. 65519
● Master station address
Station address of the master
Range of values: 0 .. 65519
● Interface
Selection of the interface for the telecontrol communication:
– LAN
– VPN
RTU3030C
Operating Instructions, 09/2017, C79000-G8976-C382-04
the redundancy combination.
Configuration (WBM)
4.20 Telecontrol
175