Siemens SIMATIC RTU3030C Operating Instructions Manual page 190

Telecontrol - rtu
Hide thumbs Also See for SIMATIC RTU3030C:
Table of Contents

Advertisement

Configuration (WBM)
4.20 Telecontrol
Signal type
Data type (bit)
Digital output
Byte (8)
Digital input
Integer without
(event counter)
sign (32)
Digital input
Floating-point
(usage meter)
number with
sign (32)
Analog input
Floating-point
number with
sign (32)
Temperature (in-
ternal),
Power supply
(external),
Battery
Analog input
Integer without
(counter)
sign (32)
Analog input
Floating-point
(analog memory
number with
bit)
sign (32)
190
TeleControl
Basic
(Data points per
object)
Cmd01B_R
(1 x 8 Commands)
Bin04B_R
(4 x 1 Byte)
Bin08X_R (8 x 1 Bit)
Counter input
Cnt01D_S (1 x 32 Bit)
32 Bit Un-
Cnt04D_S (4 x 32 Bit)
signed
Analog input
Ana04W_S (4 x 16
32 Bit Float
Bit)
Mean04W_S (4 x 16
Bit)
Set01W_S (1 x 16
Bit)
Ana04R_S (4 x 32
Bit)
Analog input
Ana04W_S (4 x 16
32 Bit Float
Bit)
Mean04W_S (4 x 16
Bit)
Set01W_S (1 x 16
Bit)
Ana04R_S (4 x 32
Bit)
Counter input
Cnt01D_S (1 x 32 Bit)
32 Bit Un-
Cnt04D_S (4 x 32 Bit)
signed
Analog input
Ana04W_S (4 x 16
32 Bit Float
Bit)
Mean04W_S (4 x 16
Bit)
Set01W_S (1 x 16
Bit)
Ana04R_S (4 x 32
Bit)
Supported data point types
ST7
DNP3
Object group [varia-
tion] *
Counter 20 [1, 2]
Frozen Counter 21
[1, 2, 5, 6]
Counter Event 22 [1,
2, 5, 6]
Frozen Counter
Event 23 [1, 2, 5, 6]
Analog Input 30 [1, 2,
5]
Analog Input Event
32 [1, 2, 3, 4, 5, 7]
Analog Input 30 [1, 2,
5]
Analog Input Event
32 [1, 2, 3, 4, 5, 7]
Counter Static 20 [1,
2]
Frozen Counter 21
[1, 2, 5, 6]
Counter Event 22 [1,
2, 5, 6]
Frozen Counter
Event 23 [1, 2, 5, 6]
Operating Instructions, 09/2017, C79000-G8976-C382-04
IEC
<type identifica-
tion>
M_IT_TB_1
<37>
M_ME_TF_1
<36>
M_ME_NA_1
<9>
M_ME_TF_1
<36>
M_ME_TF_1
<36>
M_IT_TB_1
<37>
M_ME_TF_1
<36>
RTU3030C

Advertisement

Table of Contents
loading