Configuration (WBM)
4.20 Telecontrol
● Number of lost data frames
Number of data frames that due to connection disruptions or a full send buffer could not
be sent since the last startup of the RTU.
● Reset statistics
Resets all the counters on this page to zero.
4.20.2

TeleControl Basic

Here you configure the data of the communications partner of the RTU (telecontrol server)
and the transfer settings for connection establishment.
Parameters
The following data needs to be configured:
● Active
Enable the option to enable the communication between the RTU and its communications
partner.
● IP address or DNS name of the telecontrol server
IP address or host name of the communications partner in the master station
● Interface
Selection of the interface for the telecontrol communication:
– LAN
– WAN
– VPN
● Port number
IPT listener port of TCSB
Range of values: 1024 .. 65535
With TCSB the port number 55097 is preset but can be changed.
● Project number
Number of the TCSB project
Range of values: 1 .. 2000
170
If LAN or WAN (mobile wireless) is selected, the data is encrypted using the
mechanism of the telecontrol protocol.
If VPN is selected, the data is not encrypted using the mechanism of the telecontrol
protocol but by VPN mechanisms.
If after the VPN tunnel, the connection continues via routers and further links, make
sure that the data is protected by suitable measures, e.g. by security modules
SCALANCE S/M.
Operating Instructions, 09/2017, C79000-G8976-C382-04