Avaya S8500 Manual page 69

Media server, media gateway
Hide thumbs Also See for S8500:
Table of Contents

Advertisement

2
Under the Name column, click on the first nonconfigured line (~not used~).
The system displays a new window with the following with the following configuration fields.
3
Fill in the following fields:
4
Click Save.
This is the only part you must fill out in the Alerts section. Keep the remaining fields as Avaya default
settings.
Installing the Avaya S8500 Media Server with an Avaya G650 Media Gateway
December 2003
NOTE:
Do not select the Receives Critical Alerts Only check box.
: Select Enabled from the drop-down menu.
Status
Name
: Type in a
name representing Avaya services.
method: Select one of the following from the drop-down menu:
Notification
To send alerts to INADS over modem, select IBM Director over Modem.
To send alerts to INADS over SNMP, select SNMP over LAN.
Number
:
If you select IBM Director over Modem, type in 9,18005353573 (if a direct line,
you do not need the 9,).
If you select SNMP over LAN, type in the Avaya IP address or Avaya hostname
that will receive the SNMP alerts. Additional administration must be completed in
the Network Protocols section before SNMP over LAN is used.
NOTE:
Testing the alert recipient cannot be done at this time. Please wait until all configuration
steps are completed to test the alert recipients
Configuring the Remote Supervisor Adapter
69