Configuring the SNMP modules in the uninterruptible power supplies

Setting selected traps (alarming)

The default is to set all traps, which may result in large log entries. Therefore, only set the following
traps. See the User's Guide that comes with the SNMP module for the menus and commands for setting
these traps.
UPS on Battery—Indicates AC fail with pending shutdown based on battery reserve available
UPS in Bypass—Failure either Failed UPS or overload
Replace battery—Failure of periodic (28-day) battery test indicating battery needs to be replaced.