Panasonic GTWIN Reference Manual page 184

Hide thumbs Also See for GTWIN:
Table of Contents

Advertisement

GTWIN Reference Manual
Tab
Field
List
Name
Basic Setup
Operation Mode
ON/OFF Indication
Color Setup
Image
ON Color
OFF Color
Plate
Option
Switch Sound
Display/Hide
Conditions
Valid Condition
Operation
Security
Character
Description
You can assign the configuration settings a name.
Below this field, a list displays the current configuration settings.
Bit Set: sets, i.e. turns on, the specified PLC bit device (e.g. R100)
specified in the "Device Setting" box.
Bit Reset: resets, i.e. turns off, the specified PLC bit device.
Momentary: turns on the specified PLC bit device as long as the
switch part is pressed.
Alternate: reverses the status of the specified PLC bit device (ON or
OFF) each time the switch part is pressed.
Off: the switch's appearance does not change on the GT screen
even if you press it or the status of the output destination device
changes.
On: the switch goes on or off when you press the switch part or the
status of the output destination device changes.
 Push SW: the switch goes on or off only while you are pressing
it.
Device: the switch goes on or off based on the status of the
output destination device.
The check box "Assign Output Device" refers to the device
specified for the operation mode.
The image field displays the settings you have made.
Select the color for the switch when it is ON.
Select the color for the switch when it is OFF.
Select the color for the virtual plate upon which the switch is
mounted (not for all switch types available).
Select whether a sound is produced when a switch part is pressed.
The default setting for a switch is "Display". However, you can
define the switch to be hidden and only displayed under certain
conditions, which you define in this field.
Always Operational (normal setting) or Operational under Valid
Condition. For this setting, click [Setup] to define the "Conditions"
when the switch can be used.
 Relation Device: bit, word, double word
 Relation Code: for bit, set the device to ON or OFF; for word
and double word, select the desired comparative relationship,
e.g. =, >, etc. Depending on your selection, you may have to set
the corresponding values or select a device from which to read
the value.
Reference Device: define the device used as a reference for the
relation code.
Set the security level to restrict the display and/or operation of the
part.
Change the text's language, font, style, size and color.
Click [Copy from ON] or [Copy from OFF] to copy settings made for
the switch's ON or OFF state for easy modification.
The image field displays the settings you have made.
5.1 Switch Parts
183