6.31 Integrating wattmeter
f748 : Integrating wattmeter retention selection
f749 : Integrating wattmeter display unit selection
Function
At the main power off ,it is selectable whether retention of integral output power values or not.
And also, the display unit is selectable.
The integrating wattmeter display can be cleared by external input signal by assignment of the terminal
function. Input terminal function 74, 75 (Integrating wattmeter display clear)
Title
f748
f749
6
6.32 Parameter registration to easy setting mode
f750 : EASY key function selection
f751 to f782 : Easy setting mode parameter 1 to 32
Up to 32 arbitrary parameters can be registered to easy setting mode.
Refer to section 4.5 for details.
Function
Integrating wattmeter retention selection
Integrating wattmeter display unit selection
Adjustment range
0: Disabled
1: Enabled
0:1=1kWh
1:1=10kWh
2:1=100kWh
3:1=1000kWh
F-118
E6581697
Default setting
0
Depends on
the capacity
(Refer to
section 11.4)