Details Of Bus Connection - Mitsubishi Electric GOT1000 Series Handbook

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

1. CONNECTION CONFIGURATION

4.1.3 Details of bus connection

When connecting to QCPU (Q mode)/motion controller CPU (Q series)
GOT connection conditions
Number of
Mounting distance
between main base
GOTs
*1
connected
unit and first GOT
13.2m or
less
1
13.2m or
more
13.2m or
less
2 to 5
*5
13.2m or
more
*1:
When the extension base unit is used, the extension cable length (between the base units) is included.
For the cable between the main base unit and extension base unit, refer to Mitsubishi Programmable Logic Controller MELSEC-Q (Catalog) (L(NA)-08033E).
*2:
When the first GOT is installed 13.2m or more away from the main base unit, the bus extension connector box is required.
Without the extension base unit
With the extension base unit
(The bus extension connector box cannot be mounted to the main base unit when a GOT is connected to Q00JCPU.Mount the bus extension connector box to the extension base unit.)
*3:
Select a cable to keep the total cable length between the main base unit of a programmable controller and a terminal GOT within 37m.
*4:
Indication of cable model (example) "GT15-QC B 06:0.6m"
*5:
There are the following restrictions depending on the total cable length when three or more GOTs are connected.
Use the same power supplies of a programmable controller and all GOTs and turn on or off all the power supplies simultaneously.
Number of GOTs
connected
15m or less
2 or less
3
4
5
*6:
Use the GT15-QBUS(2) for mounting the following units. GT15-75QBUS(2)L is not available.
Units for the multimedia function, Video/RGB display, RGB output, printer output, Ethernet download, gateway function, MES interface function, CF card unit, and CF card extension unit
For GT16, however, Ethernet download, gateway function, and MES interface function are available using the Ethernet interface.
*7: The bus connection unit is not required for GT115
90
4.1 MITSUBISHI Programmable Controller
4.1.3 Details of bus connection
0m
0m
Main base
Extension
Extension
unit
base unit
base unit
Cable
Max. 13.2m
Bus extension connector box
Main base
unit
Main base
Extension
unit
base unit
Max. 13.2m
Bus extension connector box
Main base
unit
: Mount the bus extension connector box to the main base unit.
: Mount the bus extension connector box to the last stage of the extension base unit.
GT15-QC06B
Total cable length
20m or less
25m or less
(dedicated to the bus connection).
System configuration
Connection distance
13.2m
13.2m
1 1
G O T
1
*1
Extension
Extension
base unit
base unit
*2
*3
Max. 37m
1
G O T
Intermediary GOT
1
Cable
Cable
*1
*3
Max. 37m
1
Cable
1
G O T
Extension
base unit
*2
1
Cable
Cable
*3
Max. 37m
: Unrestricted
: Restricted
37m or less
1
Cable
2 2 4 4
Terminal GOT
2
3
Cable
2 2 4
Intermediary GOT
Terminal GOT
2
3
Cable
5
37m
37m
1 1
G O T
2 5 5
2 5

Advertisement

Table of Contents
loading

Table of Contents