Mounting units on the GOT side interface <GT16/GT15>
stage
3rd
stage
2nd
stage
1st
Calculation of current consumed by units <GT16/15>
When using multiple units, a barcode reader, and a RFID controller, the total current consumed by the
units, barcode reader and RFID controller must be less than the current that can be supplied by the GOT.
Design the system using the following values so that the total current is within the range of the current
supply capacity of the GOT.
(1) Current that can be supplied by the GOT
(2) Current used by units, barcode reader and RFID controller
Current supply
GOT model
capacity (A)
GT1695
2.4
GT15-QBUS
GT15-QBUS2
GT1685
2.4
GT15-75QBUSL
GT1595
2.13
GT15-75QBUS2L
GT1585
1.74
GT15-ABUS
(incl. GT1585V)
GT15-ABUS2
GT157
GT15-75ABUSL
2.2
(incl. GT1575V)
GT15-75ABUS2L
GT156
2.2
GT15-RS2-9P
GT155
1.3
GT15-RS4-9S
GT15-RS4-TE
GT15-RS2T4-9P
GT15-J71E71-100
GT15-J71GP23-SX
GT15-J71LP23-25
GT15-J71BR13
GT15-J61BT13
*1 :
This value is used for calculating the current consumption of multi-channel functions.
For the specifications of each unit, see the manual supplied with each unit.
*2 :
When using a barcode reader or a RFID controller to which the power is supplied
from the standard interface, add the current to be used by the barcode reader and
RFID controller at 5VDC. (Maximum less than 0.3A)
Extension unit interface 1
Extension unit interface 2
Up to 3 communication units and optional units can be mounted on
each extension unit interface.
Mount a unit that occupies two slots on the first stage.
However, when any of the following units are used, mount the unit on the
first stage, then mount other units on the second and subsequent stages.
For GT16 (Only one of these units can be mounted on the GT16)
GT16M-V4, GT16M-R2, GT16-V4R1, GT16-ROUT, GT16M-MMR
For GT15 (Only one of these units can be mounted on the GT1585V
and GT1575V)
GT15V-75V4, GT15V-75R1, GT15V-75V4R1, GT15V-75ROUT
The following units must not be stacked on other units. Mount any of them on the first stage.
GT15-75QBUSL, GT15-75QBUS2L, GT15-75ABUSL, GT15-75ABUS2L
GT15-75J71LP23-Z, GT15-75J71BR13-Z, GT15-75J61BT13-Z
(GT16 or GT155
(Example: GT1685)
Instructions for mounting and removing the GT15-CFCD
An extension unit cannot be mounted on a CF card unit.
When extension units are mounted, mount the CF card unit on the last stage.
When mounting a CF card unit on the extension interface 1 (left), ensure
that the number of extension units mounted on the extension interface 2
(right) is smaller than the number on the extension interface 1 (left).
Otherwise, the CF card cannot be inserted or removed.
Remove the CF card unit in the designated direction ( PULL) to prevent
damage to the connector.
Standard interface (built-in RS-232 interface)
The interface can establish a serial connection with connected
devices and peripheral devices, such as a barcode reader.
Standard interface (built-in Ethernet interface) (GT16 only)
The interface can establish a connection with connected devices via Ethernet.
Standard interface (built-in RS-422/485 interface) (GT16 only)
The interface can establish a serial connection with connected devices.
Consumed
Unit model
Unit model
current (A)
Barcode reader
GT15-PRN
1
0.275*
GT16M-V4
GT15V-75V4
GT16M-R2
GT15V-75R1
0.12
GT16M-V4R1
GT15V-75V4R1
0.29
GT16M-ROUT
0.33
GT15V-75ROUT
0.3
GT16M-MMR
0.098
GT15-CFCD
0.224
GT15-CFEX-C08SET
1.07
GT15-SOUT
0.56
GT15-DIO
0.77
GT15-DIOR
0.56
RFID controller
(GT155
has the extension unit interface 1 only)
cannot be used.)
(3) Calculation example
(a) When GT15-J71BR13, GT15-RS4-9S (3 units), GT15-
Consumed
J71E71-100 (for gateway function) and barcode reader
current (A)
(0.12A) are connected to GT1575-V:
*2
GT15-RS4-9S
0.09
3rd
stage
Serial connection [4ch]
0.12
*1
GT15-RS4-9S
stage
2nd
0.2
*1
Serial connection [2ch]
*1
0
stage
1st
MELSECNET/H connection [1ch]
*1
0.2
*1
0.12
0.2
*1
0.11
*1
0.11
*1
0.27
Current supply
0.07
capacity of GOT (A)
0.15
2.2
0.77+0.33+0.33+0.33+0.224+0.12=2.104
0.08
Since the total current is within the current supply capacity of
0.1
the GOT, the units can be used.
0.1
*2
(b) When GT15-J71BR13, GT15-RS4-9S (2 units), GT15-
J71E71-100 (for gateway function) and barcode reader
(0.12A) are connected to GT1585-S:
stage
3rd
GT15-RS4-9S
2nd
stage
Serial connection [2ch]
stage
1st
MELSECNET/H connection [1ch]
Current supply
capacity of GOT (A)
1.74
Not allowed to use because the current exceeds the current
supply capacity of the GOT.
3.2 Precautions for Use
Unit occupying
two slots
Ex.: GT15-QBUS2
2 slots (1st stage)
are occupied.
GT15-J71E71-100
(for gateway function)
GT15-RS4-9S
Serial connection [3ch]
GT15-J71BR13
GT1575 main unit
Barcode reader
Total current to be consumed (A)
GT15-J71E71-100
(for gateway function)
GT15-RS4-9S
Serial connection [3ch]
GT15-J71BR13
GT1585 main unit
Barcode reader
Total current to be consumed (A)
0.77+0.33+0.33+0.224+0.12=1.774
49