1. CONNECTION CONFIGURATION
Precautions
Precautions on system
When using cyclic transmission
(1) I/O signals from/to master station
Do not turn on reserved output signals among output signals from the master station to a GOT
(remote output: RY).
When the reserved output signals are turned on, the programmable controller system may
malfunction.
(2) Applicable range for monitoring
Applicable ranges for monitoring remote I/O (RX, RY) and remote register (RWr, RWw) differ
depending on the master station mode of the CC-Link network system.
Mode of master station
Remote network mode
Remote network ver.1 mode
Remote network ver.2 mode
Remote network additional mode
When using transient transmission
(1) CC-Link module on target station
When using transient transmission to communicate with the following CC-Link modules, mount
the CC-Link module with the function version B and the software version J or later on a
programmable controller.
When communicating with the CC-Link module with the function version A and the software
version I or earlier, only the cyclic transmission is available.
• AJ61BT11 • A1SJ61BT11
• AJ61QBT11 • A1SJ61QBT11
(2) Accessible range for monitoring
A GOT can access a programmable controller CPU with the CC-Link module set as the master or
local station. The GOT cannot access other networks via the CC-Link module.
Starting GOT with CC-Link connection (intelligent device station)
When the CC-Link connection (intelligent device station) is used, the data link starts in about 10 minutes
after starting the GOT.
Precautions on setup
When changing the switch setting after installing the GT15-75J65BT13-Z type CC-Link communication
unit on a GOT, reset the GOT.
Setting [Network parameters] of GX Developer
• When [Mode] of the CC-Link module is set to [Remote net (Ver.2 mode)], [Remote station points] can
be set. The [Remote station points] setting is a setting for the remote I/O station. For a GOT, use the
default value (32 points).
• Set the station information setting to [Ver.1 Intelligent device station] when [Mode] of the CC-Link
module is set to [Remote net (Ver.2 mode)] or [Remote net(Additional mode)].
Availability of monitoring
Information of CC-Link Ver.1 compatible station
: Monitoring enabled,
*1 Available only for using GT15-J61BT13 type CC-Link communication unit.
4.1 MITSUBISHI Programmable Controller
4.1.9 CC-Link connection (intelligent device station)
Information of CC-Link Ver.2 compatible station
*1
*1
: Creating system disabled
1
2
3
4
5
6
7
155