Table 9. User Settings (continued)
Description
Start Screen
User Password
Audible Alarms
Unsynchronized Transfer to Bypass
Transfer to Bypass When Overload
Automatic Start Delay
Control Commands from X-Slot1
Control Commands from X-Slot2/Serv
X-Slot Signal Input Activation Delay
Reset Custom Event Settings
REPO Configuration

Operating Modes

Available Settings
Eaton logo
Mimic screen (see Figure 72 on page 93)
[Enabled] [Disabled]
If Enabled is selected, the password is USER.
[Normal Sound] [Disabled]
[Allowed] [Not Allowed]
[After a delay] [Immediately]
-1 through 32767 seconds
(-1 means disabled)
[Allowed] [Disabled]
Selecting Disabled prevents load commands such as Load Off
through the X-Slot, including remotely.
0 through 65 seconds
0 through 32
[Enabled][Disabled]
The BladeUPS module front panel indicates the UPS status through the UPS
indicators. Figure 71 on page 93 shows the UPS front panel indicators and controls.

Normal Mode

During Normal mode, the
UPS. The UPS monitors and charges the batteries as needed and provides filtered
power protection to your equipment.
Two settings are available for Normal Mode:
S
High Efficiency. Double-conversion on demand.
S
Standard. Continuous double-conversion.
By default, the UPS operates on a High Efficiency setting that minimizes heat
contribution to the rack environment. The system bypass input directly supplies the
system output with three-phase AC power, and the UPS stands ready to
automatically transfer to double-conversion (Standard) operation as needed. The
battery recharges when necessary.
If the input line exceeds normal operating range, the UPS transfers to Standard
operation to produce a regulated output voltage. When the input line returns to
normal operating range, the UPS returns to High Efficiency operation.
You can change the default High Efficiency setting to Standard from the front panel.
See Table 9 "User Settings" on page 96.
Eaton BladeUPS (12 kVA) User's Guide
Default Setting
Eaton logo
Disabled
Normal Sound
Not Allowed
After a delay
0s
Allowed
5s