Troubleshooting by Indication on the Remote Controller
L8
3.32 "
" Inverter Current Abnormal
L8
Remote
Controller
Display
Applicable
RXYMQ36 · 48PVJU
Models
Method of
Malfunction is detected by current flowing in the power transistor.
Malfunction
Detection
Malfunction
When overload in the compressor is detected. (Inverter secondary current 16.1A)
(1) 19.0A and over continues for 5 seconds.
Decision
(2) 16.1A and over continues for 260 seconds.
Conditions
Compressor overload
Supposed
Compressor coil disconnected
Causes
Defect of main PCB
164
SiUS34-907