Page of 264
Download Table of ContentsContents Print This PagePrint Bookmark

Daikin VRV III-S RXYMQ36 48PVJU Service Manual Page 173

60 hz.
Hide thumbs
Troubleshooting by Indication on the Remote Controller
L8
3.32 "
" Inverter Current Abnormal
L8
Remote
Controller
Display
Applicable
RXYMQ36 · 48PVJU
Models
Method of
Malfunction is detected by current flowing in the power transistor.
Malfunction
Detection
Malfunction
When overload in the compressor is detected. (Inverter secondary current 16.1A)
(1) 19.0A and over continues for 5 seconds.
Decision
(2) 16.1A and over continues for 260 seconds.
Conditions
 Compressor overload
Supposed
 Compressor coil disconnected
Causes
 Defect of main PCB
164
SiUS34-907
Troubleshooting

Advertising

This manual also for:

R-410a

Comments to this Manuals

Symbols: 0
Latest comments:
  • cp shukla Feb 16, 2016 06:50:
    RXYQ18PAY6 service manual & vrv Fulform