Page of 264
Download Table of ContentsContents Print This PagePrint Bookmark

Daikin VRV III-S RXYMQ36 48PVJU Service Manual: List Of Electrical And Functional Parts; Outdoor Unit

60 hz.
Hide thumbs
SiUS34-907

1. List of Electrical and Functional Parts

1.1
Outdoor Unit
Item
Inverter
Compressor
Crankcase heater (INV.)
Motor
Fan motor
Overcurrent relay
Electronic expansion
valve (Main)
Electronic expansion
Functional
valve (Subcooling)
parts
Four-way valve
Solenoid valve (Hot gas)
Solenoid valve (Unload circuit)
Pressure switch (INV.)
Pressure-
Fusible plug
related parts
Pressure sensor (HP)
Pressure sensor (LP)
For outdoor air
For discharge pipe
For suction pipe 1
Main
For heat exchanger
Thermistor
PCB
For suction pipe 2
For subcooling heat
exchanger
For liquid pipe
Fuse (A3P)
Others
Fuse (A1P)
Fuse (A1P)
List of Electrical and Functional Parts
Name
Symbol
Type
M1C
Output
E1HC
M1F·M2F
Cooling
Y1E
Heating
Cooling
Y3E
Heating
Y1S
Y2S
Y3S
S1PH
S1NPH
S1NPL
R1T
R2T
R3T
R4T
R5T
R6T
R7T
F1U
F4U
F6U
List of Electrical and Functional Parts
Model
RXYMQ-PVJU
JT100G-VDL@T
2.2kW
33W
0.07kW
3.2A
480pls
PI control
PI control
PI control
STF-01AQ1743A1
TEV-1620DQ2
TEV-1620DQ2
ACB-4UB10
OFF: 580+0/–21.8psi ON: 435±21.8psi
DFP-3L 158~167°F
PS8051A 0~602psi
PS8051A –7.25~247psi
3.5~360kΩ
5.0~640kΩ
3.5~360kΩ
3.5~360kΩ
3.5~360kΩ
3.5~360kΩ
3.5~360kΩ
AC250V 6.3A
AC250V 6.3A
AC250V 5.0A
Remark
(PCB terminal)
Relay
A1P X102A
A1P X28A
A1P X21A
A1P X22A
A1P X25A
A1P X26A
A1P X27A
A1P X32A
A1P X17A
A1P X18A
A1P X11A
A1P X12A 1-2Pin
A1P X12A 3-4Pin
A1P X12A 5-6Pin
A1P X12A 7-8Pin
A1P X13A 1-2Pin
A1P X13A 3-4Pin