Model
1, 3 Cooling Capacity
2, 3 Heating Capacity
Casing / Color
Dimensions: (H×W×D)
Rows×Stages×FPI
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output
Fan
Airflow Rate (HH/H/L)
External Static Pressure 4
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Gas Pipes
Piping
Connections
Drain Pipe
Machine Weight (Mass)
Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable outdoor unit
Standard Accessories
Drawing No.
Notes:
 1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB (27°CDB), 67°FWB (19.4°CWB)
Standard external static pressure
Outdoor temperature: 95°FDB (35°CDB)
Equivalent ref. piping length: 25ft (7.5 m), (Horizontal)
 2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB (21°CDB).
Standard external static pressure
Outdoor temperature: 47°FDB (8.3°CDB), 43°FWB (6°FWB)
Equivalent ref. piping length: 25ft (7.5 m), (Horizontal)
 3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
 4 External static pressure is changeable in 7 (FXMQ07, 09, 12PVJU), 14 (FXMQ18, 24, 30, 36, 48PVJU) stages within the ( )
range by remote controller.
 5 Air filter is not standard accessory, but please mount it in the duct system of the suction side.
Select its colorimetric method (gravity method) 50% or more.
Specifications
FXMQ18PVJU
Btu/h
18,000
Btu/h
20,000
Galvanized Steel Plate
11-13/16 × 39-3/8 × 27-9/16
in. (mm)
(300 x 1000 x 700)
3×16×15
ft² (m²)
2.68 (0.81)
Sirocco Fan
kw
0.04
cfm
635/582/529
"Wg
0.80-0.20
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
5
φ1/4 (6.4) (Flare Connection)
in. (mm)
φ1/2 (12.7) (Flare Connection)
in. (mm)
VP25
in. (mm)
(
External Dia. 1-1/4(31.8)
Internal Dia. 1(25.4)
Lbs (kg)
80 (36)
dBA
45/41
Fuse,
Fan Driver Overload Protector
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation Manual,
Drain Hose, Sealing Pads, Clamp
Metal, Air Discharge Flange, Air
Suction Flange
FXMQ24PVJU
24,000
27,000
Galvanized Steel Plate
11-13/16 × 39-3/8 × 27-9/16
(300 x 1000 x 700)
3×16×15
2.68 (0.81)
Sirocco Fan
0.04
688/618/565
0.80-0.20
Direct Drive
Microprocessor Thermostat for Cooling
and Heating
Glass Fiber
5
φ3/8 (9.5) (Flare Connection)
φ5/8 (15.8) (Flare Connection)
VP25
)
(
External Dia. 1-1/4(31.8)
Internal Dia. 1(25.4)
80 (36)
45/41
Fuse,
Fan Driver Overload Protector
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation Manual,
Drain Hose, Sealing Pads, Clamp
Metal, Air Discharge Flange, Air Suction
Flange
3D066117B
Specifications
FXMQ30PVJU
30,000
34,000
Galvanized Steel Plate
11-13/16 × 39-3/8 × 27-9/16
(300 x 1000 x 700)
3×16×15
2.68 (0.81)
Sirocco Fan
0.04
882/794/706
0.80-0.20
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
5
φ3/8 (9.5) (Flare Connection)
φ5/8 (15.8) (Flare Connection)
VP25
VP25
)
(
External Dia. 1-1/4(31.8)
Internal Dia. 1(25.4)
80 (36)
48/45
Fuse,
Fan Driver Overload Protector
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation Manual,
Drain Hose, Sealing Pads, Clamp
Metal, Air Discharge Flange, Air
Suction Flange
)