Page of 264
Download Table of ContentsContents Print This PagePrint Bookmark

Daikin VRV III-S RXYMQ36 48PVJU Service Manual Page 131

60 hz.
Hide thumbs
Troubleshooting by Indication on the Remote Controller
∗1: Coil check method for the moving part of the electronic expansion valve
Discount the electronic expansion valve from the PCB and check the continuity between the connector pins.
(Normal)
Pin No.
1. White
2. Yellow
3. Orange
4. Blue
5. Red
6. Brown
: Continuity
× : No continuity
122
1. White
2. Yellow
×
3. Orange
4. Blue
×
Approx. 300Ω
×
Approx. 300Ω
×
SiUS34-907
5. Red
6. Brown
×
Approx. 150Ω
×
Approx. 150Ω
×
Approx. 150Ω
×
Approx. 150Ω
×