Caution
Be sure to turn off the power switch before connecting or disconnecting the connector, or parts may be damaged.
Has a
once connected
optional controller for centralized
control been disconnected
or its address
changed?
NO
Is the
power supply
turned on for all optional
controllers for centralized
control?
YES
Is the
reset switch
of all optional controllers for
centralized control set to
"normal"?
YES
Is
transmission wiring
disconnected or wired
incorrectly?
NO
Is
a centralized remote
controller or schedule timer
connected?
NO
Are
two or more unified
ON/OFF controllers
connected?
NO
A
Troubleshooting
YES
NO
NO
YES
Is the
centralized remote
YES
controller or schedule timer
displaying a
malfunction?
NO
Is the
setting of the
YES
unified ON/OFF controller's switch
for setting each address
duplicated?
YES
Troubleshooting (OP: Unified ON/OFF Controller)
Reset power supply
simultaneously for all optional
controllers for centralized
control.
Turn on power supply for all
optional controllers for
centralized control.
Set reset switch to "normal."
Correct the wiring.
YES
Refer to failure diagnosis for
centralized remote controller or
schedule timer.
NO
Correct the setting of the unified
ON/OFF controller's switch for
setting each address and reset
the power supply of the unified
ON/OFF controller.