Troubleshooting by Indication on the Remote Controller
2.31 "L8" Outside Unit:
L8
Remote
Controller
Display
Applicable
RWEYQ60, 72, 84MTJU
Models
Method of
Malfunction is detected by current flowing in the power transistor.
Malfunction
Detection
Malfunction
When overload in the compressor is detected.
Decision
Conditions
Supposed
Causes
198
Inverter Current Abnormal
Compressor overload
Compressor coil disconnected
Defect of inverter PC board
SiUS30-604
Troubleshooting