Daikin VRV III-S RXYMQ36 48PVJU Service Manual Page 166

60 hz.
Hide thumbs
SiUS34-907
L1
3.29 "
" Malfunction of PCB
L1
Remote
Controller
Display
Applicable
RXYMQ36 · 48PVJU
Models
Method of
Malfunction is detected based on the current value during waveform output before starting
Malfunction
compressor.
Malfunction is detected based on the value from current sensor during synchronous operation
Detection
when starting the unit.
Malfunction
Overcurrent (OCP) flows during waveform output
Malfunction of current sensor during synchronous operation
Decision
IPM failure
Conditions
 Main PCB (A1P)
Supposed
Causes
Troubleshooting
IPM failure
Current sensor failure
Drive circuit failure
Troubleshooting by Indication on the Remote Controller
157

   Related Manuals for Daikin VRV III-S RXYMQ36 48PVJU