Daikin VRV III-S RXYMQ36 48PVJU Service Manual: Display "under Centralized Control" Blinks (repeats Single Blink)

60 hz.
Hide thumbs
Troubleshooting (OP: Unified ON/OFF Controller)
5.2
Display "Under Centralized Control" Blinks (Repeats
Single Blink)
Remote
Controller
Display
Applicable
Unified ON/OFF controller
Centralized remote controller, Schedule timer
Models
Method of
Detect the malfunction according to DIII-NET transmission data.
Malfunction
Detection
Malfunction
When the centralized controller, which was connected once, shows no response.
Decision
The control ranges are overlapped.
When multiple master central controllers are present
Conditions
When the schedule timer is set to individual use mode, other central controller is present.
When the wiring adaptor for electrical appendices is present
 Address duplication of optional controllers for centralized control
Supposed
 Improper combination of optional controllers for centralized control
Causes
 Connection of more than one master controller
 Malfunction of transmission between optional controllers for centralized control
 Defect of PCB of optional controllers for centralized control
206
"under centralized control" (Repeats single blink)
SiUS34-907
Troubleshooting