SiUS34-907
UH
3.47 "
" Malfunction of System, Refrigerant System Address
Undefined
UH
Remote
Controller
Display
Applicable
All indoor unit models
Models
RXYMQ36 · 48PVJU
Method of
Detect an indoor unit with no auto address setting.
Malfunction
Detection
Malfunction
The malfunction decision is made as soon as the abnormality is detected.
Decision
Conditions
Improper connection of transmission wiring between indoor and outdoor unit
Supposed
Defect of indoor unit PCB
Causes
Defect of outdoor unit PCB (A1P)
Troubleshooting
Troubleshooting by Indication on the Remote Controller
195